Vol.2 , No. 2, Publication Date: Aug. 20, 2015, Page: 17-23
[1] | E. Saafan, Electrical Engineering Department, Faculty of Engineering, University of El-Mansoura, Mansoura, Egypt. |
Multi-break vacuum technology has a high dielectric strength restoration during switching-off processes. Based on this technology, vacuum circuit breakers have more efficient breaking capability than single break during current interruption processes. In this paper, numerous simulations of transitional processes conditioned by high voltage capacitor banks switching-off were performed using multi breaks of 110kV vacuum circuit breaker. In the present work the vacuum circuit breaker is modelled by the use of PSCAD/EMTDC program. Dielectric strength of the circuit breaker based on real inter-contact distance of the multi-break vacuum has taken into account in this research. The results obtained demonstrate that, use of triple-break vacuum leads to notable decreasing of switching overvoltages and allows in the same time to meet the dielectric requirements for vacuum circuit breakers in high voltage applications more than 110kV.
Keywords
Vacuum Circuit Breaker, Multi-Break Vacuum, Inter-Contact Distance, SF 6 Circuit Breaker, Capacitor Banks, Transient Recovery Voltage, Dielectric Strength, Repeated Re-Ignitions
Reference
[01] | L. Ramming, M. Aristizabal, Cold characteristic development test of a new SF6 high voltage circuit-breaker, IEEE PES Transmission and Distribution Conference and Exposition: Latin America, Venezuela, PP. 1-4, 2006. |
[02] | Paul G. Slade, “Vacuum interrupter: Theory, Design and Application,” CRC-Press, 2007. |
[03] | M. Binnendijk, W. F. H. Merck, R. P. P. Smeets, K. Watanabe, and E. Kaneko, High-current Interruption in Vacuum Circuit Breakers, IEEE Transactions On Dielectrics and Electrical Insulation, Vol. 4, No. 6, PP. 836-840, 1997. |
[04] | P. Picot, Vacuum switching, Cahier technique Schneider Electric, no. 198, pp. 4, March 2000. |
[05] | C. Xian, D. Xiongying, and L. Minfu, The Voltage distribution characteristics of a hybrid circuit breaker during high current interruption, Plasma Science and Technology, Vol. 15, No. 8, PP. 800-806, 2013. |
[06] | S. Kulkarni, A. Kahane, and U. Sanvatsarkar, Prospects of application of vacuum switchgear at transmission voltages, proceeding of Gridtech 2013 - 4th International Exhibition & Conference, New Delhi, India, PP. 3-6, 2013. |
[07] | E. Saafan, Dielectric Strength Restoration Velocities of Multi-Break Vacuum Circuit Breakers, Engineering and Technology, Vol. 2, No. 4, PP. 215-219, 2015. |
[08] | A. Iturregi, E. Torres, I. Zamora, and O. Abarrategui, High voltage circuit-breakers: SF6 vs. vacuum, International Conference on Renewable Energies and Power Quality, Valencia, Spain, PP. 1-6, 2009. |
[09] | Xie Jiuming, Sun Dengyue, Wang Jianzhong, Cao Jianbo, and Liu Wenping, New structure design for 126kV HV vacuum circuit breaker, International Journal of Control and Automation, Vol. 7, No. 12, PP. 1-10, 2014. |
[10] | E. Schade, E. Dullni, Influencing factors of breaking capacity of double-break vacuum circuit breakers, Telkomnika, Vol. 11, No. 6, PP. 2903-2911, 2013. |
[11] | S. Giere, H. C. KÄarner, and H. Knobloch, Dielectric strength of double and single-break vacuum interrupters, IEEE Transactions on Dielectrics and Electrical Insulation Advances in Dielectric Applications, Vol. 8, No. 1, PP. 43-47, 2001. |
[12] | Liao Minfu, Duan Xiongying, and Zou Jiyan, Dielectric strength and statistical property of single and triple-break vacuum interrupters in series, IEEE Transactions on Dielectric and Electrical Insulation, Vol. 14, No. 3, PP. 600-605, 2007. |
[13] | T. Lazimov, S. Akhundov, Research on influence of high voltage circuit-breakers’ characteristics on switching overvoltages and overcurrents, proceedings of ELECO’2003 – 3rd International Conference on Electrical and Electronics Engineering, Bursa, Turkey, PP. 1-4, Dec. 2003. |